Electrical Specifications |
| |
Output ratings: |
|
|
| |
Output Voltage 1 |
|
0-10 V |
| |
Output Current 2 |
|
0-600 A |
| |
Output Power |
|
6000 W |
| |
Line Regulation: 3 |
|
|
| |
Voltage (0.01% of Vmax) |
|
1 mV |
| |
Current (0.05% of Imax) |
|
150 mA |
| |
Load regulation: 4 |
|
|
| |
Voltage (0.05% of Vmax + 5 mV) |
|
10 mV |
| |
Current (0.1% of Imax + 20 mA) |
|
150 mA |
| |
Meter accuracy: |
|
|
| |
Voltage (0.15% of Vmax) |
|
15 mV |
| |
Current (0.5% of Imax) |
|
3 A |
| |
Output noise (0-20 MHz): |
|
|
| |
Voltage (p-p) |
|
85 mV |
| |
Output ripple (rms): |
|
|
| |
Voltage |
|
10 mV |
| |
Current 5 |
|
500 mA |
| |
Drift (30 minutes): 6 |
|
|
| |
Voltage (0.04% of Vmax) |
|
4 mV |
| |
Current (0.6% of Imax) |
|
3600 mA |
| |
Drift (8 hours): 7 |
|
|
| |
Voltage (0.02% of Vmax) |
|
2 mV |
| |
Current (0.04% of Imax) |
|
240 mA |
| |
Temperature coefficient: 8 |
|
|
| |
Voltage (0.04% of Vmax/° C) |
|
4 mV |
| |
Current (0.06% of Imax/° C) |
|
360 mA |
| |
OVP adjustment range: (0 to 103% of Vmax) |
|
0-10.3 V |
| |
Efficiency: 9 |
|
85% |
| |
|
|
|
| |
1. Minimum output voltage is <0.3% of rated voltage at zero output setting. |
| |
2. Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance. |
| |
3. For input voltage variation over the AC input voltage range, with constant rated load. |
| |
4. For 0-100% load variation, with constant nominal line voltage. |
| |
5. Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode. |
| |
6. Maximum drift over 30 minutes with constant line, load, and temperature, after power on. |
| |
7. Maximum drift over 8 hours with constant line, load and temperature, after 30 minutes warm-up. |
| |
8. Change in output per ° C change in ambient temperature, with constant line and load. |
| |
9. Typical efficiency at nominal input voltage and full output power. |
| |
|
| |
General Specifications |
| |
Operational AC input voltage |
|
3-phase 190-242 VAC (47-63 Hz) (standard); 3-phase 342-500 VAC, 47-63 Hz, 3 wire and safety ground, (optional) |
| |
Input Power Factor Correction |
|
0.95 (nominal 208 Vrms), 0.9 (nominal 400 Vrms HV input option) |
| |
Remote analog programming |
|
Voltage and current programming inputs; 0-5 V, 0-10 V (default) voltage sources. Galvanically isolated from supply output. |
| |
Remote analog monitoring |
|
Voltage and current monitor outputs 0-5 V, 0-10 V (default) ranges for 0-100% of output. Galvanically isolated from supply output. |
| |
Dimensions (H x W x D) |
|
5.2 x 19.0 x 21.0" (133.5 x 483 x 533 mm) |
| |
Weight |
|
Approximately 75 lb (34 kg) |
| |
Warranty |
|
Five years |
| |
Regulatory Approvals |
| |
CE-marked units meet: EN61010-1, EN61000-6-2 and EN61000-6-4; CSA C/US certified to UL3111-1 and CSA C22.2 No 1010.1 Meets USA EMC standard: FCC, part 15B, class A; Meets Canadian EMC standard: ICES-001 Class A. |
| |
| Note: Specifications subject to change without notice. |
|