| General Specifications |
|
|
|
| |
GT100-208 |
GT100-480 |
GT250-480 |
| Maximum continuous output power |
100 kW |
100 kW |
250 kW |
| Nominal output voltage |
208 Vac |
480 Vac |
480 Vac (line to line, +10%-12%) |
| Nominal output frequency |
60 Hz |
60 Hz |
60 Hz (+0.5 Hz / -3.0 Hz) |
| Nominal output current |
278 A rms |
120 A rms |
301 A rms |
| Maximum output fault current |
1100 A peak |
1100 A peak |
1400 A peak (duration of 0.008 sec) |
| Power factor |
> 0.99 |
> 0.99 |
> 0.99 |
| DC input voltage range |
300-600 Vdc |
300-600 Vdc |
300-600 Vdc |
| Peak power tracking voltage range |
300-480 Vdc |
300-480 Vdc |
300-480 Vdc |
| Maximum input current |
347 Adc |
347 Adc |
867 Adc |
| Maximum input short-circuit current |
460 Adc |
460 Adc |
1214 Adc |
| Maximum backfeed current |
0 Adc |
0 Adc |
0 Adc |
| Peak inverter efficiency |
96.2% |
96.70% |
96.80% |
| CEC efficiency |
95.0% |
96.00% |
96.00% |
| Night-time power consumption |
< 100 W |
< 100 W |
< 100 W |
| Maximum output over-current protection |
400 A |
200 A |
400 A |
|
|
|
|
| Mechanical Specifications |
|
|
|
| Operating temperature range |
-5°F to 122°F (-15° to 50°C) |
|
|
| Enclosure rating |
NEMA 3R (outdoor rating) |
|
|
| Enclosure |
E-coated and powder coated steel enclosure |
|
| Unit weight |
3000 lb (1361 kg) |
3000 lb (1361 kg) |
4000 lb (1814 kg) |
| Inverter dimensions (H x W x D) |
73.3 x 67.0 x 46.1” |
73.3 x 67.0 x 46.1” |
86.3 x 90.0 x 46.1“ |
| |
1862 x 1702 x 1171 mm |
1862 x 1702 x 1171 mm |
2192 x 2286 x 1171 mm |
| |
|
|
(Removable air intake reduces depth |
| |
|
|
by 12” for fitting through doors) |
| Noise |
< 70 dBA |
|
|
| Altitude |
up to 6600’ (2012 m) without de-rating |
|
| Relative humidity |
0 to 95% non-condensing |
|
|
|
|
|
|
| Features & Options |
|
|
|
| Cooling method |
Forced convection cooling/sealed design |
|
| AC/DC disconnect |
Standard and integrated within the inverter enclosure |
|
| Isolation transformer |
Standard and integrated within the inverter enclosure |
|
| User display |
Standard bright fluorescent green vacuum display |
|
| Ground-fault detection/interruption |
Standard and integrated within the inverter enclosure |
|
| Communications |
Optional RS485/Modbus and RS232 communications |
|
| Sub-array combiner |
Optional and integrated within the inverter enclosure, 100 A circuits, other sizes available |
|
|
|
|
| Regulatory Approvals |
|
|
|
| Certified to UL 1741 (2005 Edition) and CSA 107.1-01 |
|
|
| Tested to IEEE 1547 |
|
|
|
| FCC Part 15 Class A |
|
|
|
|
|
|
|
| Specifications subject to change without notice. |
|
|