Xantrex brings the next generation of inverter/charger to market, with the XW Hybrid Inverter/Charger, the heart of the XW System. The XW Hybrid Inverter/Charger (XW) is a true sine wave, 120/240-volt AC, split-phase, inverter/charger that incorporates a DC to AC inverter, a battery charger, and an AC auto-transfer switch. It is the foundation for battery- based residential and commercial applications up to 18 kilowatts (kW). Capable of being grid-interactive or grid-independent, the XW can operate with generators and renewable energy sources to provide full time or backup power.

For more information on the XW Hybrid Inverter/Charger, please visit the XW System website


 
Product Info | Specifications | Document Downloads | Compare
 

Specifications

Electrical Specifications      
Model  XW6048-120/240-60  XW4548-120/240-60 XW4024-120/240-60
Continuous output power  6,000 W 4500 W 4000 W
Surge rating (10 seconds) 12,000 W 9000 W 8000 W
Surge current L-N: 105 Arms (7 sec) L-L: 52.5 Arms (7 sec) L-N: 75 Arms (20 sec)
  L-L: 40 Arms (20 sec) L-N: 70 Arms (20 sec) L-L: 35 Arms (20 sec)
Waveform  True sine wave True sine wave True sine wave
Low-load efficiency  95% 95% 95%
Idle consumption - search mode < 8 W < 8 W < 8 W
AC connections  AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator) AC1 (Grid), AC2 (Generator)
AC voltage  120/240 Vac split-phase 120/240 Vac split-phase  120/240 Vac split-phase
AC input breaker 60 A two-pole 60 A two-pole 60 A two-pole
Utility interactive Yes Yes Yes
CEC weighted efficiency  92.50% 93% 91%
CEC power rating  5752 W  4500 W  4000 W
AC input voltage range (bypass/charge mode) L-N: 80 - 150 Vac (120 V nominal); L-L: 160 - 270 Vac (240 V nominal)
AC input frequency range (bypass/charge mode) 55 - 65 Hz (default); 44 - 70 Hz (allowable)
AC1 voltage range – Sell mode  L-N: 108 - 130 +/- 1.5 Vac; L-L: 214 - 260 +/- 3.0 Vac
(automatically adjusts when entering Sell mode)*      
AC1 frequency range – Sell mode  59.4 - 60.4 +/- 0.05 Hz
(automatically adjusts when entering Sell mode)*      
AC output voltage L-N: 120 Vac +/- 3%; L-L: 240 Vac +/- 3%    
AC output frequency 60.0 +/-0.1 Hz    
DC current at rated power   130 A 96 A 178 A
Total harmonic distortion < 5%    
Automatic transfer relay 60 A    
Typical transfer time 8 ms    
DC input voltage (nominal)  50.4 Vdc  50.4 Vdc  25.2 Vdc
DC input voltage range  44 - 64 Vdc 44 - 64 Vdc  22 - 32 Vdc
Maximum continuous charge rate 100 A 85 A 150 A
Efficiency at maximum charge rate  89.40% 90.20% 85.80%
Power factor corrected charging  0.98 0.98 0.98
Emissions  FCC Class B  FCC Class B  FCC Class B
Multiple-unit configurations Up to three parallel units in 120/240-volt split- phase configuration    
     
Auxiliary relay output  0-12 Vdc, maximum 250 mA DC    
Non-volatile memory  Yes  Yes  Yes
System network  Xanbus™ (publish-subscribe network, no need for hubs or special cards) 
       
       
Mechanical Specifications      
Mounting Wall mount, backplate included    
Inverter dimensions (H x W x D) 23 x 16 x 9” (580 x 410 x 230 mm)    
Inverter weight 121.7 lb (55.2 kg) 118 lb (53.5 kg) 116 lb (52.5 kg)
Shipping dimensions 28 x 22 ¼ x 10 ½” (711 x 565 x 267 mm)    
Shipping weight 169 lb (76.7 kg) 165 lb (75 kg) 163 lb (74 kg)
Display panel  Status LEDs indicate AC In status, faults/warnings, equalize mode, battery level. Three-character display indicates output power or charge current, fault/warning codes. On/Off and equalize buttons
 
Battery temperature sensor Included Included Included
Standard warranty Five years Five years Five years
Part number 865-1000 865-1005 865-1010
Environmental Specifications      
Enclosure type NEMA Type 1 – Indoor (sensitive electronic components sealed inside enclosure) 
Operational temperature range -13 to 158 °F (-25 to 70 °C)    
Accessories      
Remote display Optional XW System Control Panel monitors and configures all devices connected to Xanbus™ Network
Generator support Optional XW Automatic Generator Start module connects to Xanbus™ Network. Automatically activates generator to recharge depleted battery bank or assist inverter with heavy loads 
   
Power distribution & panel conduit boxes Optional balance-of-systems components for NEC compliant installations, includes pre-wired AC and 
  DC circuit breakers, bus barsand multiple knockouts  for conduit and additional breakers
Regulatory Approval      
UL 1741 1st Edition: 2005 Version CSA 107.1-01      