| Electrical Specifications |
|
|
|
| Model |
XW6048-120/240-60 |
XW4548-120/240-60 |
XW4024-120/240-60 |
| Continuous output power |
6,000 W |
4500 W |
4000 W |
| Surge rating (10 seconds) |
12,000 W |
9000 W |
8000 W |
| Surge current |
L-N: 105 Arms (7 sec) |
L-L: 52.5 Arms (7 sec) |
L-N: 75 Arms (20 sec) |
| |
L-L: 40 Arms (20 sec) |
L-N: 70 Arms (20 sec) |
L-L: 35 Arms (20 sec) |
| Waveform |
True sine wave |
True sine wave |
True sine wave |
| Low-load efficiency |
95% |
95% |
95% |
| Idle consumption - search mode |
< 8 W |
< 8 W |
< 8 W |
| AC connections |
AC1 (Grid), AC2 (Generator) |
AC1 (Grid), AC2 (Generator) |
AC1 (Grid), AC2 (Generator) |
| AC voltage |
120/240 Vac split-phase |
120/240 Vac split-phase |
120/240 Vac split-phase |
| AC input breaker |
60 A two-pole |
60 A two-pole |
60 A two-pole |
| Utility interactive |
Yes |
Yes |
Yes |
| CEC weighted efficiency |
92.50% |
93% |
91% |
| CEC power rating |
5752 W |
4500 W |
4000 W |
| AC input voltage range (bypass/charge mode) |
L-N: 80 - 150 Vac (120 V nominal); L-L: 160 - 270 Vac (240 V nominal) |
| AC input frequency range (bypass/charge mode) |
55 - 65 Hz (default); 44 - 70 Hz (allowable) |
| AC1 voltage range – Sell mode |
L-N: 108 - 130 +/- 1.5 Vac; L-L: 214 - 260 +/- 3.0 Vac |
| (automatically adjusts when entering Sell mode)* |
|
|
|
| AC1 frequency range – Sell mode |
59.4 - 60.4 +/- 0.05 Hz |
| (automatically adjusts when entering Sell mode)* |
|
|
|
| AC output voltage |
L-N: 120 Vac +/- 3%; L-L: 240 Vac +/- 3% |
|
|
| AC output frequency |
60.0 +/-0.1 Hz |
|
|
| DC current at rated power |
130 A |
96 A |
178 A |
| Total harmonic distortion |
< 5% |
|
|
| Automatic transfer relay |
60 A |
|
|
| Typical transfer time |
8 ms |
|
|
| DC input voltage (nominal) |
50.4 Vdc |
50.4 Vdc |
25.2 Vdc |
| DC input voltage range |
44 - 64 Vdc |
44 - 64 Vdc |
22 - 32 Vdc |
| Maximum continuous charge rate |
100 A |
85 A |
150 A |
| Efficiency at maximum charge rate |
89.40% |
90.20% |
85.80% |
| Power factor corrected charging |
0.98 |
0.98 |
0.98 |
| Emissions |
FCC Class B |
FCC Class B |
FCC Class B |
| Multiple-unit configurations |
Up to three parallel units in 120/240-volt split- phase configuration |
|
|
| |
|
|
|
| Auxiliary relay output |
0-12 Vdc, maximum 250 mA DC |
|
|
| Non-volatile memory |
Yes |
Yes |
Yes |
| System network |
Xanbus™ (publish-subscribe network, no need for hubs or special cards) |
| |
|
|
|
| |
|
|
|
| Mechanical Specifications |
|
|
|
| Mounting |
Wall mount, backplate included |
|
|
| Inverter dimensions (H x W x D) |
23 x 16 x 9” (580 x 410 x 230 mm) |
|
|
| Inverter weight |
125 lb (57 kg) |
115 lb (52 kg) |
115 lb (52 kg) |
| Shipping dimensions |
28 x 22 ¼ x 10 ½” (711 x 565 x 267 mm) |
|
|
| Shipping weight |
132 lb (60 kg) |
122 lb (55 kg) |
122 lb (55 kg) |
| Display panel |
Status LEDs indicate AC In status, faults/warnings, equalize mode, battery level. Three-character display indicates output power or charge current, fault/warning codes. On/Off and equalize buttons |
| |
|
| Battery temperature sensor |
Included |
Included |
Included |
| Standard warranty |
Five years |
Five years |
Five years |
| Part number |
865-1000 |
865-1005 |
865-1010 |
|
|
|
|
| Environmental Specifications |
|
|
|
| Enclosure type |
NEMA Type 1 – Indoor (sensitive electronic components sealed inside enclosure) |
| Operational temperature range |
-13 to 158 °F (-25 to 70 °C) |
|
|
|
|
|
|
| Accessories |
|
|
|
| Remote display |
Optional XW System Control Panel monitors and configures all devices connected to Xanbus™ Network |
| Generator support |
Optional XW Automatic Generator Start module connects to Xanbus™ Network. Automatically activates generator to recharge depleted battery bank or assist inverter with heavy loads |
| |
|
| Power distribution & panel conduit boxes |
Optional balance-of-systems components for NEC compliant installations, includes pre-wired AC and |
| |
DC circuit breakers, bus barsand multiple knockouts for conduit and additional breakers |
|
|
|
|
| Regulatory Approval |
|
|
|
| UL 1741 1st Edition: 2005 Version CSA 107.1-01 |
|
|
|
|
|
|
|
| Specifications subject to change without notice. |
|
|
|