Electrical Specifications - Inverter |
|
|
Output power (continuous) |
|
3000 watts |
|
|
Surge rating (5 seconds) |
|
7500 watts (60 A) |
|
|
Output voltage |
|
120 VAC |
|
|
Output frequency |
|
60 Hz +/- 0.05% (crystal controlled) |
|
|
Output waveform |
|
Sine wave (< 5% THD) |
|
|
Peak Efficiency |
|
> 90% |
|
|
Efficiency (full load) |
|
> 85% |
|
|
No load power draw (search mode) |
|
< 20 W |
|
|
AC connections |
|
Split phase in / dual out |
|
|
AC transfer capability |
|
2 legs at 50 A (split phase in), 2 legs at 30 A (dual in) |
|
|
Transfer time |
|
20 ms (typical) |
|
|
Electrical Specifications - Charger |
|
|
Output current |
|
150 A DC |
|
|
Battery voltage (nominal) |
|
12 VDC |
|
|
Battery voltage range |
|
10.0 - 15.5 VDC |
|
|
Charge control |
|
3 stage with manual equalize |
|
|
Charge temperature compensation |
|
Remote battery sensor (included) |
|
|
Efficiency |
|
85% typical |
|
|
AC input power factor |
|
0.95 |
|
|
Input current (for 150 A charging) |
|
22 A RMS nominal |
|
|
AC input voltage |
|
120 VAC nominal |
|
|
AC input voltage range |
|
90 - 135 VAC |
|
|
Compatible battery types |
|
Wet/Gel/AGM |
|
|
General Specifications |
|
|
Operating temperature range |
|
-4°F - 122°F (-20°C - 50°C) |
|
|
Storage temperature range |
|
-40°F - 122°F (-40°C - 50°C) |
|
|
Dimensions (HxWxD) |
|
8.17 x 13.25 x 16" (208 x 336 x 406 mm) |
|
|
Weight |
|
75.0 lb (34.0 kg) |
|
|
Warranty |
|
3 years |
|
|
Part number |
|
809-3000 (Split phase in / Dual out) |
|
|
Accessories |
|
System Control Panel
Automatic Generator Start
Network Cable 3'
Network Cable 25’
Network Cable 50’
Network Cable 75’
|
809-0910
809-0915
809-0935
809-0940
809-0941
809-0942
|
|
|
Regulatory Approvals |
|
|
CSA/NRTL certified to CSA 107.1, UL 458 |
|
|
FCC Class B/Industry Canada Class |
|
|
|
Note: The product information provided in this specification sheet is preliminary and is subject to change |