Electrical Specifications |
|
|
Utility Interactive Protection |
|
Over/under AC voltage and frequency detection plus active islanding detection |
|
|
AC Voltage (Nominal) |
|
120 VAC |
|
|
AC Voltage (Allowed): |
|
|
|
|
Utility Interactive Mode |
|
106 - 132 VAC |
|
|
Bypass Mode (Adjustable) |
|
80 - 149 VAC inverter controlled |
|
|
Frequency (Allowed): |
|
|
|
|
Utility Interactive Mode |
|
59.3 - 60.5 Hz |
|
|
Bypass Mode (Adjustable) |
|
53.0 - 67.0 Hz inverter controlled |
|
|
AC Current (Allowed at 25 C): |
|
|
|
|
Utility Interactive Mode |
|
40 amps continuous |
|
|
Bypass Mode (Adjustable) |
|
60 amps continuous |
|
|
Total Output Harmonic Distortion |
|
|
|
|
Rated |
|
< 5% at full power |
|
|
Typical |
|
2.5% at full power |
|
|
Power Factor (Allowed) |
|
> 94% |
|
|
General Specifications |
|
|
Enclosure Type |
|
Indoor, ventilated, steel chassis with white, powder coat finish |
|
|
Unit Weight |
|
26 lb (11.8 kg) |
|
|
Dimensions (H x W x D) |
|
6.3 x 21.0 x 7.0" (16 x 53.3 x 17.8 cm) |
|
|
Mounting |
|
Wall mount in a horizontal position only with a mounting bracket |
|
|
AC Input/Output Terminals |
|
Sized for #2 - 14# AWG wire |
|
|
Conduit Sizes |
|
Dual 3/4" - 1" and 1/2" - 3/4" knockouts available |
|
|
Warranty |
|
Two years |
|
|
Part Number |
|
GTI |
|
|
Regulatory Approvals |
|
|
CSA Listed to UL1741 - 1st Edition |
|
|
UL Listed to UL1741 - 1st Edition |
|
|
|
Note: Specifications subject to change without notice. |