Electrical Specifications |
|
|
Continuous Power Rating |
|
100 kW (208 and 480 models) |
|
|
Nominal AC Input Voltage |
|
208 VAC (480 VAC) Three-phase, +10% / -12% |
|
|
Nominal AC Input Frequency |
|
60 Hz +0.5 Hz / -0.7 Hz |
|
|
Line Power Factor |
|
>0.99 Above 20% rated power |
|
|
Maximum AC Line Current |
|
278 amps AC at 208 VAC, 121 amps AC at 480 VAC |
|
|
AC Current Distortion |
|
<5% THD at rated power |
|
|
Max. Open Circuit Voltage |
|
600 VDC |
|
|
Power Tracking Window Range |
|
300 to 600 VDC |
|
|
Max. DC Input Current |
|
357 amps DC |
|
|
CEC Efficiency |
|
95% (480V), 94.5% (208V) |
|
|
Peak Inverter Efficiency |
|
>95% |
|
|
Standby Tare Losses |
|
<100 watts |
|
|
General Specifications |
|
|
Temperature Range: |
|
|
Ambient |
|
-4° F to 122° F (-20° C to 50° C) |
|
|
Storage |
|
-40° F to 122° F (-40° C to 50° C) |
|
|
Enclosure Environmental Rating |
|
NEMA3R |
|
|
Enclosure |
|
Powder coated Galvanneal folded steel enclosure |
|
|
Weight (inverter) |
|
1000 lb (499 kg) |
|
|
Weight (transformer) |
|
1400 lb (635 kg) (Includes AC Interface Enclosure) |
|
|
Inverter Dimensions (H x W x D) |
|
82 x 60.25 x 22" (208 x 153 x 56 cm) |
|
|
Transformer Dimensions |
|
44 x 50 x 34” (112 x 127 x 86 cm) |
|
|
Altitude |
|
6,600' (2,012 m) |
|
|
Relative Humidity |
|
0 to 95% non-condensing, both models |
|
|
Array Configuration |
|
Monopole, negative and positive grounded, both models |
|
|
Features & Options |
|
|
Cooling Method |
|
Forced convection cooling |
|
|
Protective Functions |
|
AC over/under voltage, AC over/under frequency, ground over current, over temperature, AC and DC over current, DC over voltage |
|
|
User Display |
|
Standard - LCD, four-line, eighty-characters, with on/off toggle switch |
|
|
AC Disconnect |
|
Standard - NEMA3R wall mount enclosure, 600 VDC load break rated; integral to inverter assembly |
|
|
DC Disconnect |
|
Standard - NEMA3R wall mount enclosure, 600 VDC load break rated; integral to inverter assembly |
|
|
Isolation Transformer |
|
High efficiency, Wye-Wye isolation transformer standard and integral to inverter assembly |
|
|
Combiner Enclosures |
|
Optional - 10 or 12 pole, with or without diodes, NEMA3R wall mount enclosure |
|
|
Communications Software |
|
Optional- Serial communications and control software |
|
|
Regulatory Approvals |
|
|
Certified to UL Standard 1741, UL File No. E199356 |
|
|
|